The VP range of products protect electrical equipment and installations against transient overvoltage that may arise in the electrical supply. Besides, the VP range can be classified into 3 different types (C, B, B+C) which provide the highest protection level in order to prevent damages in the electrical equipment and financial losses.

  • Compact equipments for all distribution systems
  • High discharge capacity via zinc oxide varistors and gas deschargers
  • With thermal separation device
  • Visual indication of a fault in the equipment
  • Remote signalling of the protection status
  • Plug-in protection modules which facilitate maintenance
Contact us

    Name (required)

    Lastname (required)

    Email (required)

    Company (required)




    Select your Country*

    Your message (required)

    This site is protected by reCAPTCHA and the Google
    Privacy Policy and
    Terms of Service apply.

    Code4164841642416434164441645416464164141647
    ModelVP B25 255/NPEVP B25 275/1VP B25 275/1+NPEVP B25 275/2VP B25 275/2+NPEVP B25 275/3VP B25 275/3+NPEVP B25 275/4
    According to IEC 61643-1 (Class)Class IClass IClass IClass IClass IClass IClass IClass I
    Type of networkTTTT/TNTT/TNTNTT/TNTNTT/TNTN
    Electrical line-1P+NPE1P+N+PE1P+N+PE 2P+NPE2P+N+PE2P+N+PE 3P+PE 3P+NPE3P+N+PE 3P+PE3P+N+PE
    Nominal voltage Un (Vac)230 Vac230 Vac230 Vac230 Vac230 Vac230 Vac230 Vac230 Vac
    Maximum continuous operating voltage Uc (Vac)255Vac275Vac275Vac275Vac275Vac275Vac275Vac275Vac
    Nominal discharge current (8/20 ?s) In (kA)50 kA50 kA50 kA50 kA50 kA50 kA50 kA50 kA
    Maximum discharge current (8/20 μs) Imax (kA)100 kA100 kA100 kA100 kA100 kA100 kA100 kA100 kA
    Impulse current (10/350 μs) Iimp (kA)25 kA25 kA25 kA25 kA25 kA25 kA25 kA25 kA
    Protection level Up (kV) @ 25 kA (10/350 μs)< 1.8 kV< 1.8 kV< 1.8 kV< 1.8 kV< 1.8 kV< 1.8 kV< 1.8 kV< 1.8 kV
    Response time ta (ns)< 100 ns< 25 ns< 25 ns< 25 ns< 25 ns< 25 ns< 25 ns< 25 ns
    Maximum back-up fuse (A gL/gG)160160160160160160160160
    Nº Modules11223344
    Code4163141632416334163641637416384163941640
    ModelB+C60 255/NPEB+C60 275/1B+C60 275/1+NPEB+C60 275/2B+C60 275/2+NPEB+C60 275/3B+C60 275/4B+C60 275/3+NPE
    According to IEC 61643-1 (Class)Class I+IIClass I+IIClass I+IIClass I+IIClass I+IIClass I+IIClass I+IIClass I+II
    Type of networkTTTT/TNTT/TNTNTT/TNTNTNTT/TN
    Electrical line-1P+NPE1P+N +PE1P+N+PE 2P+NPE2P+N+PE2P+N+PE 3P+PE 3P+NPE3P+N+PE3P+N+PE 3P+PE
    Nominal voltage Un (Vac)230 Vac230 Vac230 Vac230 Vac230 Vac230 Vac230 Vac230 Vac
    Maximum continuous operating voltage Uc (Vac)255Vac275Vac275Vac275Vac275Vac275Vac275Vac275Vac
    Impulse current (10/350 μs)7 kA7 kA7 kA7 kA7 kA7 kA7 kA7 kA
    Nominal discharge current (8/20 μs) In (kA)30 kA30 kA30 kA30 kA30 kA30 kA30 kA30 kA
    Maximum discharge current (8/20 μs) Imax (kA)60 kA60 kA60 kA60 kA60 kA60 kA60 kA60 kA
    Protection level Up (kV) at 30 kA< 1.5 kV< 1.5 kV< 1.5 kV< 1.5 kV< 1.5 kV< 1.5 kV< 1.5 kV< 1.5 kV
    Response time ta (ns)< 25 ns< 25 ns< 25 ns< 25 ns< 25 ns< 25 ns< 25 ns< 25 ns
    Maximum back-up fuse (A gL/gG)125125125125125125125125
    Nº Modules11223344
    Code41600416024160341604416074160641610416094162441625
    ModelVP C40 275/1VP C40 250/NPEVP C40 275/2VP C40 275/1 + NPEVP C40 275/3VP C40 275/2 + NPEVP C40 275/4VP C40 275/3 + NPEVP C20 275/1 + NPEVP C20 275/3 + NPE
    According to IEC 61643-1 (Class)Class IIClass IIClass IIClass IIClass IIClass IIClass IIClass IIClass IIClass II
    Type of networkTT/TNTTTT/TNTTTT/TNTTTT/TNTTTTTT
    Electrical line1P+N+PE 2P+N+PE 3P+PE 3P+N+PE1P+N 2P+N 3P+N 3P1P +N+PE 2P +NPE1P+N2P+N+PE 3P+PE 3P+NPE2P+N3P+N+PE3P+N 3P1P+N3P+N 3P
    Nominal voltage Un(Vac)230 Vac230 Vac230 Vac230 Vac230 Vac230 Vac230 Vac230 Vac230 Vac230 Vac
    Maximum continuous operating voltage Uc(Vac)275 Vac250 Vac275 Vac275 Vac275 Vac275 Vac275 Vac275 Vac275 Vac275 Vac
    Nominal discharge current (8/20 μs) In (kA)20202020202020201010
    Maximum discharge current (8/20 μs) Imax (kA)40404040404040402020
    Protection level Up (kV)< 1.2< 1.5< 1.2< 1.2< 1.2< 1.2< 1.2< 1.2< 1.0< 1.0
    Protection level at 5 kA (kV)< 1.0--< 1.0< 1.0< 1.0< 1.0< 1.0< 1.0< 0.95< 0.95
    Response time ta (ns)< 25<100<25<25<25<25<25<25<25<25
    Maximum back-up fuse (A gL/gG)125--125125125125125125100100
    Nº Modules1122334424
    Plug-in modules Code41611416124161141611 /416124161141611 /416124161141611 /4161241626 /4162741626 /41627