| SELECTION TABLE | ANSI CODE | SIA-B Specific | SIA-B Standard | SIA-C | SIA-F | SIL-A | SIL-G | SIL-C | SIL-S | SIU-C | SIR-A | SIR-C |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| TYPE | ||||||||||||
| SELF & DUAL POWERED (SELF+AUX) | √ | √ | √ | |||||||||
| AUXILIARY POWERED | √ | √ | √ | √ | √ | √ | √ | √ | ||||
| INSTRUMENTS TRANSFORMER | ||||||||||||
| Conventional Current Transformer input | 3 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | |||
| Conventional Voltage Transformer input | 1 | 5 | 5 | 5 | ||||||||
| Non-Conventional LPCT/Rogowsky input | 3 | |||||||||||
| Non-Conventional LEA input | 3 | 6 | 6 | |||||||||
| APPLICATIONS | ||||||||||||
| Feeder | √ | √ | √ | √ | √ | √ | √ | |||||
| Transformer | √ | √ | √ | √ | √ | |||||||
| Generator | √ | √ | √ | |||||||||
| Capacitor Bank | √ | √ | √ | √ | √ | √ | √ | √ | ||||
| Arc flash | √ | √ | ||||||||||
| Recloser | √ | √ | ||||||||||
| Seccionalizer | √ | √ | ||||||||||
| RTU | √ | √ | ||||||||||
| Wind Power | √ | √ | √ | √ | √ | √ | √ | |||||
| Solar Power | √ | √ | √ | √ | √ | √ | √ | |||||
| Grid Interconnection | √ | √ | √ | √ | √ | √ | ||||||
| FUNCTIONS | ||||||||||||
| Instantaneous phase overcurrent | 50 | √ | √ | √ | √ | √ | √ | √ | √ | √ | √ | |
| Inverse time phase overcurrent | 51 | √ | √ | √ | √ | √ | √ | √ | √ | √ | √ | |
| Inverse Time Directional Phase Overcurrent | 67 | √ | √ | √ | √ | √ | ||||||
| Instantaneous Neutral overcurrent | 50N/G | √ | √ | √ | √ | √ | √ | √ | √ | √ | √ | |
| Inverse time Neutral overcurrent | 51N/G | √ | √ | √ | √ | √ | √ | √ | √ | √ | √ | |
| Inverse Time Directional Neutral Overcurrent | 67N/G | √ | √ | √ | √ | √ | √ | |||||
| Directional isolated neutral overcurrent | 67NI/GI | √ | √ | √ | √ | √ | ||||||
| Incipient/Intermittent Fault detection | 50INC | √ | √ | √ | ||||||||
| Switch On To Fault | SOTF | √ | √ | √ | √ | √ | √ | √ | √ | √ | ||
| Phase balance current protection | 46 | √ | √ | √ | √ | √ | √ | √ | √ | |||
| Broken Conductor Detection | 46BC | √ | √ | √ | √ | √ | √ | √ | ||||
| Restricted Earth Fault | 64REF | √ | √ | √ | √ | √ | √ | |||||
| Thermal overload | 49 | √ | √ | √ | √ | √ | √ | √ | √ | √ | √ | |
| External Trip | 49T | √ | √ | √ | √ | √ | √ | √ | √ | √ | √ | |
| Trip block for switch | TB | √ | √ | √ | √ | |||||||
| Instantaneous phase undercurrent | 37 | √ | √ | √ | √ | √ | √ | √ | ||||
| Second Harmonic Blocking | SHB | √ | √ | √ | √ | √ | √ | √ | √ | √ | ||
| Instantaneous phase overvoltage | 59 | √ | √ | √ | √ | √ | √ | |||||
| Instantaneous Neutral Overvoltage | 59N/G | √ | √ | √ | √ | √ | √ | √ | ||||
| Phase Balance voltage protection | 47 | √ | √ | √ | √ | √ | √ | |||||
| Instantaneous Phase undervoltage | 27 | √ | √ | √ | √ | √ | √ | |||||
| Inverse Time Positive sequence undervoltage | dv/dt | √ | ||||||||||
| Directional Overpower | 32 | √ | √ | √ | √ | √ | ||||||
| Under/Overfrequency | 81O/U | √ | √ | √ | √ | √ | √ | |||||
| Rate of change of Frequency (ROCOF) | 81R | √ | √ | √ | √ | √ | √ | |||||
| Out of Step (Vector Shift) | 78 | √ | √ | √ | √ | √ | √ | |||||
| Overfluxing | 24 | √ | √ | √ | ||||||||
| Cold Load pickup | CLP | √ | √ | √ | √ | √ | √ | √ | √ | √ | ||
| AC Reclosing device | 79 | √ | √ | √ | √ | √ | √ | √ | √ | |||
| Sequence Coordination Mode | SCM | √ | √ | |||||||||
| Sectionalizer Mode | SZM | √ | √ | |||||||||
| Breaker wear monitoring | 52 | √ | √ | √ | √ | √ | √ | √ | √ | √ | √ | |
| Synchro Check | 25 | √ | √ | √ | √ | √ | √ | |||||
| Hot Line Tag | HLT | √ | √ | √ | √ | √ | √ | |||||
| Circuit Breaker Failure | 50BF | √ | √ | √ | √ | √ | √ | √ | √ | √ | √ | |
| Trip Circuit Supervision | 74TCS | √ | √ | √ | √ | √ | √ | √ | √ | |||
| Close Circuit Supervision | 74CCS | √ | ||||||||||
| Phase CT Supervision | 60CTS | √ | √ | √ | √ | √ | √ | √ | ||||
| Phase LPVT Supervision | 60VTS | √ | √ | √ | √ | √ | ||||||
| Trip lockout | 86 | √ | √ | √ | √ | √ | √ | √ | √ | |||
| Zone selection interlocking (ZSI) | 68 | √ | √ | √ | √ | √ | √ | √ | √ | √ | ||
| Power Supply Control | PSC | √ | √ | √ | √ | |||||||
| Programmable logic control | PGC | √ | √ | √ | √ | √ | √ | √ | √ | √ | √ | √ |
| Load Management System | LMS | √ | √ | √ | √ | √ | ||||||
| Fault Locator | 21FL | √ | √ | √ | √ | |||||||
| Arc Flash Detection | AFD | √ | √ | |||||||||
| ADDITIONAL FEATURES | ||||||||||||
| Counters | √ | √ | √ | √ | √ | √ | √ | √ | √ | √ | ||
| Commands | √ | √ | √ | √ | √ | √ | √ | √ | √ | √ | √ | |
| Setting Groups | 2 | 4 | 3 | 3 | 4 | 4 | 4 | 4 | 4 | 6 | 6 | |
| Digital Inputs | Up to 1 | Up to 3 | Up to 10 | Up to 2 | up to 9 | Up to 24 | Up to 11 | Up to 11 | Up to 11 | Up to 24 | Up to 11 | |
| Digital Outputs | Up to 2 | Up to 3 | Up to 7 | Up to 3 | Up to 7 | Up to 18 | Up to 7 | up to 7 | Up to 7 | Up to 18 | Up to 7 | |
| Polarized Tripping Output | 1 | 1 | 1 | |||||||||
| LEDs | 2+1 mag. Indicator | 4 | 7+1 mag. Indicator | 3 | 8 | 11 | 11 | 11 | 11 | Up to 24 | 11 | |
| LCD | 20x2 LCD | 20x2 LCD | 20x2 LCD | 20x2 LCD | 20x2 LCD | 20x4 LCD | 20x4 LCD | 20x4 LCD | 20x4 LCD | 20x4 LCD | 20x4 LCD | |
| Key-pad | 8 | 8 | 9 | 7 | 11 | 13 | 13 | 13 | 13 | Up to 21 | 13 | |
| Event records | 100 | 1024 | 1024 | 200 | 2048 | 3072 | 3072 | 3072 | 3072 | 3072 | 3072 | |
| Fault Reports | Up to 4 | Up to 20 | Up to 20 | Up to 4 | Up to 100 | Up to 100 | Up to 100 | Up to 100 | Up to 100 | Up to 100 | Up to 100 | |
| Oscillography records (COMTRADE) | Up to 10 | Up to 10 | 1 | Up to 100 | Up to 100 | Up to 100 | Up to 100 | Up to 100 | Up to 100 | Up to 100 | ||
| Load Data Profiling (LDP) | √ | √ | √ | √ | √ | √ | n/a | √ | √ | |||
| Local Port (frontal) | Micro USB | Micro USB | Micro USB | Micro USB | Micro USB | Micro USB | Micro USB | Micro USB | Micro USB | Micro USB | Micro USB | |
| COMMUNICATIONS PROTOCOLS | ||||||||||||
| ModBus RTU | √ | √ | √ | √ | √ | √ | √ | √ | √ | √ | √ | |
| IEC60870-5-103 | √ | √ | √ | √ | √ | √ | √ | √ | ||||
| DNP3.0 Serial | √ | √ | √ | √ | √ | √ | √ | √ | √ | √ | ||
| Modbus TCP/IP | √ | √ | √ | √ | √ | √ | √ | √ | ||||
| DNP3 TCP/IP | √ | √ | √ | √ | √ | √ | √ | |||||
| IEC 60870-5-104 | √ | √ | √ | √ | √ | √ | √ | |||||
| IEC61850 | √ | √ | √ | √ | √ | √ | √ | |||||
| SNTP | √ | √ | √ | √ | √ | √ | √ | |||||
| Web Server | √ | √ | √ | √ | √ | √ | √ | |||||
| IRIG-B | √ | √ | √ | √ | √ | √ | ||||||
| REMOTE PORT (REAR) | ||||||||||||
| RS485 | √ | √ | √ | √ | √ | √ | √ | √ | √ | √ | √ | |
| RJ45 | √ | √ | √ | √ | √ | √ | √ | √ | ||||
| RS232 | √ | |||||||||||
| FO | √ | √ | √ | √ | √ | √ | √ | |||||
| MONTAGE | ||||||||||||
| Panel mounted | √ | √ | √ | √ | √ | √ | √ | √ | √ | √ | √ | |
| UL | ||||||||||||
| UL certified | √ | √ | √ |