Key Features :
- Self-powered via standard CTs (/5 or /1).
- Universal auxiliary supply: 24–230 V AC/DC, USB, or power bank.
- Optional internal battery (20-year lifetime) for commissioning.
- Very low start-up levels: 0.075xIn (3-phase), 0.16xIn (1-phase).
- Metal enclosure, high EMC, wide temperature range.
- Front keypad, configurable LEDs, and magnetic trip indicator.
- Self-diagnostics and test menu before energizing.
- Communication ports: front USB, optional RS485 and Ethernet.
- Trip output for low-power coil (24 Vdc – 135 mJ).
- I/O options: up to 7 outputs + 10 inputs.
- Load Data Profiling: 168 circular records; sampling interval configurable 1–60 min.
- Non-volatile RAM stores up to 1024 event and disturbancefault recordings (DFR) with internal RTC; multiple COMTRADE/ data recording options with pre/post-fault cycles.
- Oscillography in COMTRADE, downloaded via SICom.
- Withdrawable and fixed versions, no external batteries needed.
- Eliminates the need for installing and maintaining external batteries, reducing operating costs of the facility.

![SIAC-Y_IZQUIERDA_1[1]](https://www.fanox.com/wp-content/uploads/2025/08/SIAC-Y_IZQUIERDA_11-400x400.png)