SIA-F protection relay is suitable to protect installations against O/C and E/F. Its compact size makes this relay adequate for installition where the space is critical. Optionally, other protection functions as the thermal image (ANSI 49) the trip block for switch disconnector and control functions as the monitorization of the CB (ANSI 52), The breaker failure (ANSI 50BF) can be included.

Besides, its special mechanic with the current transformers in charge of the measurement outside, allow the user to change the transformation ratio (by giving turnes throgh the holes of these current transformers.

The relay is designed to work with standard current transformers (1 A or 5 A of secondary) and is able to measure up to 30 times the nominal current.  It is provided with local and rear communications, with optional protocols as Modbus RTU or DNP3.0 Serial.
Up to 3 outputs and 2 inputs are included in the relay to monitor and signal different situations in the installation.

The SIA-F is able to record up to 200 events, 4 fault reports and 1 oscillografic records in non-volatile RAM memory with the date and time thanks to its internal real clock (RTC)
Thanks to its versatility and to its compact size, this relay can be used in a lot of applications.

Main Applications: Secondary Distribution, RMUs and SF6 insulated Switchgears

Contact us

    Name (required)

    Lastname (required)

    Email (required)

    Company (required)




    Select your Country*

    Your message (required)

    This site is protected by reCAPTCHA and the Google
    Privacy Policy and
    Terms of Service apply.

    The SIA-F is an overcurrent protection relay with a switched auxiliary power supply (24-220 Vdc / 48-230 Vac). The current is measured by using /5 or /1 current transformers. The relay can be also power supplied by a USB cable connected to the laptop or an standard power bank.

    • Protection functions: 50, 50/51, 50N/G, 50/51 N/G, CLP, 86, PLC.
    • Trip block for switch disconnector, 49, 49T, 52, 50BF, 68 as optionals.
    • High electromagnetic compatibility.
    • With circuit breaker control and monitoring (circuit breaker status, number of openings, accumulated amperes, etc.).
    • Compact size with reduced depth makes it easier to install and saves costs.
    • USB connection on the front (Modbus RTU communication protocol).
    • A specific test menu is provided.
    • There are three configurable LED indicators on the front of the SIA-F equipment. By default, they indicate indicate if the equipment is On (LED ON), if an alarm has happened (LED ALARM) or if a trip has happened (LED TRIP).
    • Programmable logic (PLC)
    • 1 Oscillographic record, non-volatile RAM memory in order to store up to 200 events and 4 fault reports, without power supply thanks to its internal RTC (Real Time Clock)

    50 Phase instantaneous overcurrent
    50/51 Phase inverse time overcurrent
    50N/G Neutral instantaneous overcurrent measured/calculated
    50/51N/G Neutral inverse time overcurrent measured/calculated
    52 Circuit breaker monitoring
    49T
     External trip
    68 Trip Bus
    86 Trip output lockout with PLC
    CLP
     Cold Load Pick-up
    50BF Circuit breaker opening fault
    49 Thermal Image
    TB Trip Block for switch disconnector

    Communication Software for SIA & SIL protection relays

    The SICom PC software has been designed and programmed to gain access to all of Fanox relays information, to modify the settings and configuration, check states and measurements and to analyse and save events and fault reports using a graphic-friendly user interface.

    SICom software works with the Windows® Windows 7, Windows 8, Windows 8.1 and Windows 10 operating system.

    • General data reading: Complete model, Version, Serial number, etc.
    • States reading
    • Measurements reading
    • Reading and changing settings
    • Reading and changing configuration
    • Reading and deleting events
    • Reading and deleting fault reports
    • Reading and deleting demand current (load data profiling)
    • Reading and saving oscillographic records in Comtrade format
    • Changing the user passwords
    • Saving and Loading settings files
    • Saving and Loading configuration files
    • Saving events and fault reports
    • Saving demand current (load data profiling)
    • Date-time synchronization
    • Configuring the communication parameters
    • Reading and changing counters
    • Commands for opening and closing the circuit breaker and block/unblock the recloser
    • Configuration of the inputs
    • Configuration of the outputs
    • Configuration of the causes that start a Fault Report

    The update of the software does not require any user´s action, this is, if the computer is connected to Internet, SICom updates itself when it is started.
    It will allow you to prepare all the settings and relay configurations without having the relay connected to the PC (offline mode), reducing engineering and commissioning time.
    SICom program uses Modbus protocol, so only the ports with this protocol can be used to establish the communication.

    SIA RANGESIA-B Specific CT'sSIA-B Standard CT'sSIA-C Standard CT'sSIA-F
    TYPESELF & DUAL POWERED (SELF+AUX)SELF & DUAL POWERED (SELF+AUX)SELF & DUAL POWERED (SELF+AUX)AUXILIARY POWERED
    Auxiliary Supply24Vdc
    110Vac
    230Vac
    24-230 Vac/dc24Vdc
    230Vac
    48 Vdc
    110-230 Vac/Vdc
    24-220 Vcc / 48-230 Vac
    Self Power Supply3.2 A for CT08-5 6.4 A for CT16-5 12.8 A for CT32-5 25.6 A for CT64-5 51.2 A for CT128/5 102.4 A for CT256/5 (x3)0,075 In (x3)0,1 In (x3)
    External batteryUSB cable / Power bankUSB cable / Power bankKITCOMUSB cable / Power bank
    Internal battery√ (*)√ (*)
    Consumption0,5 W1,5 W0,5 W1,5 – 2,2 W
    CTSpecific CTStandard CT/1A - 2VAStandard CT/1A - 2.5VA Standard CT/5A - 5VAStandard CT/1 - 0,5VA Standard CT/5A - 0.5VA
    501221
    50G221
    50N1
    511111
    51G111
    51N1
    SHB11
    74CT1
    46BC1
    4611
    791
    52111
    50BF111
    491111
    49T1111
    CLP111
    74TCS 1
    Trip Block111
    68 Zone Selection interbloking111
    86
    PGCProgrammable LogicV3V3V3V3
    Counters
    Commands
    Sett. Group243/43
    Inputs--- EXT.TRIP3 DI--- EXT.TRIP 2DI 2DI + EXT.TRIP--- 2DI
    Outputs--- 2NC-NO3 NC-NO--- 2 NC-NO 3 NO1 NO + 1 NC-NO
    Output for STRIKER24 Vdc – 135 mJ24 Vdc – 135 mJ24 Vdc – 135 mJ
    LEDs2 LEDs 2 LEDs +1MAG.FLAG4 LEDs3 LEDs + 1 MAG.FLAGS 3 LEDs + 3 MAG.FLAGS3 LEDs configurable
    HMI20X2 LCD + 7/8 keys20X2 LCD + 8 keys20X2 LCD + 7/8 keys20X2 LCD + 7 keys
    Event10010241024200
    Fault Report420204
    Oscillography10 records x 50 cycles10 records x 50 cycles1 record x 22 cycles
    Current demand
    Local Port (frontal)USBMicro USBRS232USB
    Remote Port (rear)RS485RS485RS485RS485
    Communications ProtocolsModBus RTUModBus RTU ModBus RTU or DNP3.0ModBus RTU ModBus RTU or IEC60870-5-103ModBus RTU DNP3.0
    Size of (HxW)Vertical: 120,65 x 167,80 mm
    Horizontal: 185,80 x 102,7 mm
    90 X 245 mmVertical Compact: 177 x 155 mm
    Vertical Standard: 177 x 189 mm
    Horizontal: 177,8 x 290,3 mm
    167,80 x 120,65 mm