KitCom
 
The KitCom is an adapter to conect a 9 V battery to the SIA through the front RS232 communication port. The adapter allows the use of 9 V battery supply and communication through the port at the same time. The use of the KitCom to supply the equipment with a 9 V battery ensures the complete operability of the SIA, even the tripping in case of a fault.
 
SICom Program
 
Our software SICOM, on Windows 2000/XP, allows access to all information of SI device, modify settings and save events using a graphical user interface. The program can be used locally through the front port or remotely through the rear port RS485.
 
 
Percutor
 
It is a solenoid of simple effect, the stroke from the initial position to the end position, is made by a spring incorporated in the solenoid. When the solenoid is in the end position, the mechanical rearment to the beginning position is made by external forces that act on the plunger, compressing the spring and storing mechanical energy. The core and the spring are retained in the initial position by magnets. To free them, it is necessary to send to the coil a polarized electrical low-voltage signal, so the stroke is made.

 

Standard voltage: 6 to 24 Vcc

 

Protection rate: IP-40

 

Type

Stroke “s” (mm)

Winding Resistance

Spring Force (N)±10%

Mechanical response time (ms)

Magnetic retention force (N)

Dimensions (mm)

WeightKg

Begin of stroke

End of stroke

A

B

C

D

E

ECI35

8

38

37

18

4

10

44,5

49

56

64

42,5

0,190

 

 

Trip Adapter(TCM)

 

For the SIA-C and SIA-E, a coil trip adapter module is available (TCM). The adapter, provides the stored energy to trip the coil. The adapter, once loaded, is capable of maintainig the power for 3 days in absence of auxiliary supply.
 
FANOX Transformers

 

Current transformer for internal use, without primary winding, with 2 secondaries, one for protection and another for self-powering. Associable with protection relays for secondary cells.
 

 

Ip/Is(A)

VA

Class

Ext

1S1-1S2 Protection (green)

100/1

0,12

5P30

120%

2S1-2S2 Supply (yellow)

60/1

0,31

Supply

 
 

0,72/3 kV

50-60 Hz

Insulation class B

EIC 60044-1

Ith: 20kA-1s / Idyn: 50kA